Electrical Data for Hydraulic 3 Phase Motors in a Dry Mount Power Unit |
| HP |
VOLT |
Full Load Amps |
Locked Rotor Amps |
| 15 |
200, 208 |
46.2 |
279 |
| 220, 230, 240 |
42 |
242 |
| 440, 460, 480 |
21 |
121 |
| 20 |
200, 208 |
60 |
261 |
| 220, 230, 240 |
52 |
224 |
| 440, 460, 480 |
26 |
112 |
| 25 |
200, 208 |
73 |
331 |
| 220, 230, 240 |
63 |
290 |
| 440, 460, 480 |
32 |
145 |
| 30 |
200, 208 |
83 |
419 |
| 220, 230, 240 |
72 |
351 |
| 440, 460, 480 |
36 |
175 |
| 40 |
200, 208 |
109 |
495 |
| 220, 230, 240 |
94 |
424 |
| 440, 460, 480 |
47 |
212 |
| 50 |
200, 208 |
133 |
667 |
| 220, 230, 240 |
116 |
562 |
| 440, 460, 480 |
58 |
281 |
|
|
|
|
| |
|
| HP |
VOLT |
Full Load Amps |
Locked Rotor Amps |
| 60 |
200, 208 |
160 |
833 |
| 220, 230, 240 |
140 |
724 |
| 440, 460, 480 |
70 |
362 |
| 75 |
220, 230, 240 |
174 |
800 |
| 440, 460, 480 |
87 |
400 |
| 100 |
230 |
230 |
1004 |
| 460 |
115 |
502 |
|
|